The Fluke 1732 (without wifi) and 1734 (with wifi) Three Phase Electrical Energy Loggers deliver easy to use three phase power measurement data for discovering sources of electrical energy waste, overloaded circuits and help you perform routine load studies. Discover when and where energy in your facility is being consumed - from the service entrance to individual circuits. Access and share three phase power data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins.
Get the Fluke Guide to Choosing Power Quality Tools
Profiling energy usage across your facility helps you identify opportunities for energy savings, and provides you with the data you need to act on them. The new Energy Analyze software package allows you to compare multiple data points over time to build a complete picture of energy usage, which is the first step to reduce the cost of your energy bill.
*Not all models are available in all countries. Check with your local Fluke representative.
| Three-phase Energy Loggers | Three-phase Power Loggers | |||
|---|---|---|---|---|
| Features | 1732 Energy Logger | 1734 Energy Logger | 1736 Power Logger | 1738 Advanced Power Logger |
| Load studies | • | • | • | • |
| Energy assessments | • | • | • | • |
| Neutral Current, 4th current channel | • | • | ||
| Harmonics measurements | • | • | ||
| Voltage event capture | • | • | ||
| PQ Health Graphical overview (EN50160) | Upgrade package* | • | ||
| IEEE519 total harmonic distortion | Optional | Optional | ||
| Fully integrated logging with Fluke Connect® | Upgrade package* | • | Upgrade package* | • |
| WiFi | Optional | • | • | • |
| Wi-Fi / Bluetooth | Optional | • | Optional | • |
| Magnetic probe set | Optional | • | Optional | • |
| Magnetic hanger | Optional | • | Optional | • |
| Connection via WiFi router | Requires FREE software license available upon product registration. | Requires FREE software license available upon product registration. | ||
| Specifications | |||||
| Accuracy | |||||
| Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale) | ||
| Voltage | 1000 V | 0.1 V | ±(0.2% + 0.01%) | ||
| Current: Direct input | i17xx-flex 1500 12" | 150 A | 0.1 A | ±(1% + 0.02%) | |
| 1500 A | 1 A | ±(1% + 0.02%) | |||
| i17xx-flex 3000 24" | 300 A | 1 A | ±(1% + 0.03%) | ||
| 3000 A | 10 A | ±(1% + 0.03%) | |||
| i17xx-flex 6000 36" | 600 A | 1 A | ±(1.5% + 0.03%) | ||
| 6000 A | 10 A | ±(1.5% + 0.03%) | |||
| i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
| 40 A | 10 mA | ±(0.7% + 0.02%) | |||
| Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%) | ||
| Auxillary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
| Voltage min/max | 1000 V | 0.1 V | ±(1% + 0.1%) | ||
| Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
| THD on voltage | 1000% | 0.1% | ±0.5 | ||
| THD on current | 1000% | 0.1% | ±0.5 | ||
| Intrinsic Uncertainty ±(% of reading +% of range)¹ | |||||
| Parameter | Influence quantity | iFlex1500-12 | iFlex3000-24 | iFlex6000-36 | i40S-EL |
| 150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
| Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Active Energy Ea | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Apparent Energy Eap | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
| Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
| Reactive Energy Er | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
| Power Factor PF | - | ±0.025 | |||
| Displacement Power Factor | - | ±0.025 | |||
| DBF/cosϕ | - | ±0.025 | |||
| Additional uncertainty in% of range¹ | VP-N>250 V | 0.015% | 0.0225% | 0.0225% | 0.015% |
¹Range = 1000 V x Irange
| |||||